5. Output function
5.1 Switching outputs
The EDS 300 has 1 or 2 switching outputs. The following settings can be made under the
basic setting:
5.1.1 Switching point setting (SP)
One switching point and one hysteresis can be set for each switching output. The respective
output switches when the pre-set switching point is reached and switches back when the
pressure falls below the switch-back point. The switch-back point is determined by the pre-
set hysteresis (switch-back point = switching point minus hysteresis).
Abbreviations: "S.P.1", "S.P.2" = switching point 1 or 2
"h.Y.1", "h.Y.2" = hysteresis 1 or 2
5.1.2 Window function setting (WIN)
The window function enables a range to be monitored. For each switching output, in each
case an upper and a lower switching value can be input which determine the range.
The respective output switches when the pressure enters this range. Upon leaving the
range, i.e. when the switch-back value has been reached, the output switches back. The
lower switch-back value is just below the lower switching value (lower switching value minus
three times the increment, see point 5.4). The upper switch-back value is just above the
upper switching value (upper switching value plus three times the increment, see point 5.4).
The area between switching and switch-back value forms a safety zone which prevents
unwanted switching operations from occurring (e.g. triggered by pulsations from a pump).
Example for switching output 1 (normally open function):
Abbreviations: "hi.1", "hi.2"= High level 1 or 2 = upper switching value 1 or 2
"Lo.1", "Lo.2"= Low level 1 or 2 = lower switching value 1 or 2
Note: The window function only operates correctly (switching on and off), when all switching
values (including the safety zone) are greater than 0 bar and lower than the nominal
pressure range.
5.2 Analogue output
On specified models, the EDS 300 provides one analogue output with a 4...20 mA signal.
5.3. Setting the Switching Points and Hystereses
Lo.1
hi.1 plus 3xincrement
Lo.1 minus 3xincrement
P
t
Safety zone
Safety zone
On
Off
Off
On
ON
Off
Switch-back valuet
Switching value
Switch-back value
Switching value